TRICONEX 3700/TRICONEX 3700A Analog Input Module Specifications.
Analog Input (AI) Modules includes three independent input channels. Each input channel receives variable voltage signals from each point, converts them to digital values, and transmits the values to the three Main Processor modules on demand. In TMR mode, one value is then selected using a midvalue selection algorithm to ensure correct data for every scan.
Sensing of each input point is performed in a manner that prevents a single failure on one channel from affecting another channel. Each Analog Input Module sustains complete, ongoing diagnostics for each channel. Failure of any diagnostic on any channel activates the Fault indicator for the module, which in turn activates the chassis alarm signal. The module’s Fault indicator merely reports a channel fault, not a module failure—the module can operate properly with as many as two faulty channels.
Analog Input Modules support hot-spare capability, which allows online replacement of a faulty module.Analog Input Modules require a separate external termination panel (ETP) with a cable interface to the Tricon backplane. Each module is mechanically keyed for proper installation in a Tricon chassis.
UFC921A101 3BHE024855R0101 Interface board INT-2 contains the main software
PFSK151 3BSE018876R1 Signal processing board
GFD563A102 3BHE046836R0102 丨AC800 PEC丨Performance controller rectifier field