TRICONEX 3721 Analog Input Module Specifications:
Highway Addressable Remote Trans-ducer (HART) is an industry standard field bus protocol that superimposes a Frequency Key Shifted (FSK) signal onto the 4-20 mA loop. The Tricon Model 2071H HART Multiplexer Module that is incorporated into each of the HART Interface Modules capaci-tively couples the HART signal to the AI or AO signals. The HART signals are approximately ±0.5 mA at 1,200 and 2,200 Hz. These frequencies are high enough that the low-bandwidth loop is unaffected and the HART elec-tronics can impose and extract the HART signals easily
Voltage:0 to 5 VDC or -5 to +5 VDC1 , + 6%
Type: TMR, AI
No. of Input Points: 32 differential, DC-coupled
Isolated Points:Yes
Input Update Rate:10 ms
Resolution: 12 bits or 14 bits programmable
Accuracy:< 0.15% of FSR from 0° to 60° C
Input Resistance (load):10 M (DC), min.
Power-Off Resistance:140 k (DC), typical
Common Mode Rejection: -85 dB (DC – 100 Hz)
Common Mode Range:-12V to +12V peak
Analog Input Modules support hot-spare capability, which allows online replacement of a faulty module.Analog Input Modules require a separate external termination panel (ETP) with a cable interface to the Tricon backplane. Each module is mechanically keyed for proper installation in a Tricon chassis.
UFC921A101 3BHE024855R0101 Interface board INT-2 contains the main software
PFSK151 3BSE018876R1 Signal processing board
GFD563A102 3BHE046836R0102 丨AC800 PEC丨Performance controller rectifier field
DS200DCFBG1B DC power feedback board丨EX2000 Series